PRODUCTS::Boiler Controls
Hegwein Pilot Burner ZA0, tube Ø 1.89 in.(48 mm.)

 
Heat Release:
Max. 419,000 BTU / 120 kW
Flame Length:
max. 23.62 in. / 600 mm
Pilot Burner Tube Length:
9.45 - 393.70 in. /
240 - 10,000 mm
 
Gas Inlet:
1/2", from left or right
Gas Pressure:
50 -150 mbar
Air Inlet:
1", may be rotated in increments of 90°
Air Pressure:
15 mbar, depending on tube length
Transformer:
Ignition:
5 kV
Ambient Temperature:
32 to 140°F / 0 to 60°C
Protection Class:
IP 54
1. Igniter Head
2. Electrical Plug (female)
3. Gas Pressure Test Nipple
4. Allen Screws
5. Air Pressure Test Nipple

6. Pilot Burner Tube with Mounting Flange
7. Intermediate Support Ring
8. Connecting Rods
9. Gas Tube
10. Final Electrode Support Ring
11. Gas Nozzle
12. Mixing Chamber with Mixing Ring
13. Gasket
13. Gasket

Refer to www.durag.com for more information.

 
 